Div. B › Part 8 › 8.4 › 8.4.2 — Design and Construction Requirements

8.4.2.3 — Sizing

Copied!
(1) A Class 2 sewage system shall be designed and constructed so that the loading rate to the side walls shall be not more than the value calculated using the formula,
LR = 400 / T
where,
LR =loading rate of the sidewalls in litres per day/m2, and
T =percolation time.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.