Div. B › Part 8 › 8.7 › 8.7.2 — Design and Construction Requirements

8.7.2.3 — Leaching Chambers within Leaching Beds

Copied!
(1) Leaching chambers are permitted for use in conjunction with an absorption trench, shallow buried trench, filter bed or Type A dispersal bed.
(2) Leaching chambers shall comply with the dimension requirements for either a Type I or Type II leaching chamber listed in Table 8.7.2.3.
(3) Leaching chambers shall conform to the requirements of IAPMO PS 63, “Plastic Leaching Chambers”.
(4) The header line and leaching chambers within a leaching bed shall be designed and constructed so that they can be detected by,
(a) magnetic means,
(b) means of a 14 gauge TW solid copper light coloured plastic coated tracer wire, or
(c) other means of subsurface detection.
Tables & Figures referenced
Table 8.7.2.3 : Leaching Chamber Dimensions : Forming Part of Sentence 8.7.2.3.(2)
Loading Table 8.7.2.3…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.