Div. B › Part 8 › 8.7 › 8.7.3 — Absorption Trench Construction

8.7.3.1A — Length of Leaching Chamber

Copied!
(1) The total length of leaching chamber shall,
(a) not be less than 30 m when constructed as a shallow buried trench, or
(b) not be less than 40 m for any other absorption trench.
(2) Except as provided in Sentences (1) and (3), the total length of leaching chamber shall not be less than the value determined by the formula,
L = QT/200, for a Type I leaching chamber, or
L = QT/300, for a Type II leaching chamber,
where,
L =total length of leaching chamber in metres,
Q =the total daily design sanitary sewage flow in litres, and
T =the design percolation time.
(3) When a treatment unit described in Article 8.6.2.2. is used in conjunction with a leaching chamber, the total length of leaching chamber shall not be less than the value determined by the formula,
L = QT/300
where,
L =total length of leaching chamber in metres,
Q =the total daily design sanitary sewage flow in litres, and
T =the design percolation time.
(4) Except as provided in Sentence (1), where the leaching bed is constructed as a shallow buried trench, the total length of leaching chamber shall not be less than the value determined by Table 8.7.3.1A.
Tables & Figures referenced
Table 8.7.3.1A : Length of Leaching Chamber in Shallow Buried Trench : Forming Part of Sentence 8.7.3.1A.(4)
Loading Table 8.7.3.1A…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.