8.8.2.1 — Construction Requirements

Copied!
(1) All Class 5 sewage systems shall be equipped with a device that shall produce an audible and visual warning alarm so located to warn that the sewage system is nearing capacity.
(2) The device required in Sentence (1) shall be designed to provide suitable advance warning to the building occupants considering,
(a) the total daily design sanitary sewage flow,
(b) the location of the Class 5 sewage system, and
(c) the response time of the hauled sewage system contractor.
(3) Except as provided in Sentence (4), all holding tanks shall be provided with a vent that,
(a) is not less than 3 in. trade size,
(b) terminates at least,
(i) 300 mm above finished grade with a vent cap, or
(ii) 600 mm above finished grade with a vent cap when the holding tank is located in an area subject to flooding, and
(c) terminates at least 3.5 m away from any air inlet, window, or door.
(4) A vent from a holding tank may connect into the venting system of the building served by the holding tank provided that,
(a) the vent is not less than 3 in. trade size, and
(b) the installation of the vent shall conform to the requirements in Part 7.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.