Div. B › Part 4 › 4.1 › 4.1.5 — Live Loads Due to Use and Occupancy

4.1.5.6 — Loads for Dining Areas

Copied!
(1) The minimum specified live load listed in Table 4.1.5.3. for dining areas may be reduced to 2.4 kPa for areas in buildings that are being converted to dining areas, provided that the floor area does not exceed 100 m² and the dining area will not be used for other assembly purposes, including dancing.
Tables & Figures referenced
Table 4.1.5.3 : Specified Uniformly Distributed Live Loads on an Area of Floor or Roof : Forming Part of Sentence 4.1.5.3.(1)
Loading Table 4.1.5.3…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.