Div. B › Part 4 › 4.1 › 4.1.6 — Loads Due to Snow and Rain

4.1.6.6 — Horizontal Gap between a Roof and a Higher Roof

Copied!
(1) Where the roof of one building is separated by a distance, a, from an adjacent building with a higher roof as shown in Figure 4.1.6.5.A., the influence of the adjacent building on the value of the accumulation factor, Ca, for the lower roof shall be determined as follows:
(a) if a > 5 m, the influence of the adjacent building on Ca need not be considered, and
(b) if a ≤ 5 m, Ca for the lower roof shall be calculated in accordance with Article 4.1.6.5. for values of x ≥ a.
Tables & Figures referenced
Table 4.1.6.5.A : Snow Load Factors for Lower Level Roofs : Forming Part of Sentences 4.1.6.5.(1) and (3) and 4.1.6.6.(1)
Loading Figure 4.1.6.5.A…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.