Div. B › Part 4 › 4.1 › 4.1.7 — Wind Load

4.1.7.9 — Full and Partial Wind Loading

Copied!
(1) Except where the wind loads are derived from the combined CpCg values determined in accordance with Article 4.1.7.6., buildings and structural members shall be capable of withstanding the effects of,
(a) the full wind loads acting along each of the two principal horizontal axes considered separately,
(b) the wind loads as described in Clause (a) but with 100% of the load removed from any one portion of the area,
(c) the wind loads as described in Clause (a) but with both axes considered simultaneously at 75% of their full value, and
(d) the wind loads as described in Clause (c) but with 50% of these loads removed from any portion of the area.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.