Div. B › Part 4 › 4.1 › 4.1.6 — Loads Due to Snow and Rain

4.1.6.9 — Gable Roofs

Copied!
(1) For all gable roofs, the full and partial load cases defined in Article 4.1.6.3. shall be considered.
(2) For gable roofs with a slope of > 15°, the unbalanced load case shall also be considered by setting the values of the accumulation factor, Ca, as follows:
(a) on the upwind side of the roof peak, Ca shall be taken as 0, and
(b) on the downwind side of the roof peak, Ca shall be taken as,
(i) 0.25 + /20, where 15° ≤ ≤ 20°, and
(ii) 1.25, where 20° < ≤ 90°.
(3) For all gable roofs, the slope factor, Cs, shall be as prescribed in Sentences 4.1.6.2. (5) and (6).
(4) For all gable roofs, the wind exposure factor, Cw, shall be,
(a) as prescribed in Sentences 4.1.6.2. (3) and (4) for the full and partial load cases, and
(b) 1.0 for the unbalanced load case referred to in Sentence (2).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.