Div. B › Part 4 › 4.1 › 4.1.6 — Loads Due to Snow and Rain

4.1.6.7 — Areas Adjacent to Roof Projections

Copied!
(1) Except as provided in Sentences (2) and (3), the accumulation factor, Ca, for areas adjacent to roof-mounted vertical projections shall be calculated in accordance with Sentence 4.1.6.5. (1) using the following values for the peak accumulation factor, Ca0, and the drift length, xd:
(a) Ca0 shall be taken as the lesser of,
0.67 · (γ h / (C_b S_s)) and (γ l_o / (7.5 C_b S_e)) + 1
(b) xd shall be taken as the lesser of,
(i) 3.35h, and
(ii) (2/3)l0,
where,
h =height of the projection, and
l0 =longest horizontal dimension of the projection.
(2) Ca is permitted to be calculated in accordance with Article 4.1.6.5. for larger projections.
(3) Where the longest horizontal dimension of the roof projection, l0, is less than 3 m, the drift surcharge adjacent to the projection need not be considered.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.