Div. B › Part 7 › 7.3 › 7.3.4 — Support of Piping

7.3.4.4 — Support for Vertical Piping

Copied!
(1) Except as provided in Sentence (2), vertical piping shall be supported at its base and at the floor level of alternate storeys by rests, each of which can bear the weight of pipe that is between it and the rest above it.
(2) The maximum spacing of supports shall be 7.5 m.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.