Div. B › Part 7 › 7.4 › 7.4.2 — Connections to Drainage Systems

7.4.2.3 — Direct Connections

Copied!
(1) Two or more fixture outlet pipes that serve outlets from a single fixture that is listed in Clause 7.4.2.1. (1) (d) may be directly connected to a branch that,
(a) has a size of at least 1 ¼ in., and
(b) is terminated above the flood level rim of a directly connected fixture with a minimum diameter waste of 1 ½ in. to form an air break.
(2) Fixture drains from fixtures that are listed in Subclauses 7.4.2.1. (1) (d) (i) and (ii) may be directly connected to a pipe that,
(a) is terminated to form an air break above the flood level rim of a fixture that is directly connected to a sanitary drainage system, and
(b) is extended through the roof when fixtures that are on 3 or more storeys are connected to it.
(3) Fixture drains from fixtures that are listed in Subclauses 7.4.2.1. (1) (d) (iii) to (vi) may be directly connected to a pipe that,
(a) is terminated to form an air break above the flood level rim of a fixture that is directly connected to a storm drainage system, and
(b) is extended through the roof when fixtures that are on 3 or more storeys are connected to it.
(4) Every waste pipe carrying waste from a device for the display, storage, preparation or processing of food or drink shall be trapped and have a minimum diameter equal to the diameter of the drain outlet from the device.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.