Div. B › Part 7 › 7.5 › 7.5.5 — Miscellaneous Vent Pipes

7.5.5.5 — Provision for Future Installations

Copied!
(1) Where provision is made for a fixture to be installed in the future, the drainage system and venting system shall be sized accordingly and provision made for the necessary future connections.
(2) Except as required in Sentence 7.5.7.7. (2), where a plumbing system is installed in a building, every storey in which plumbing is or may be installed, including the basement of the building, shall have extended into it or passing through it a vent pipe that is at least 1 ½ in. in size for the provision of future connections.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.