Div. B › Part 7 › 7.5 › 7.5.4 — Vent Pipes for Soil or Waste Stacks

7.5.4.5 — Fixtures Draining into Vent Pipes

Copied!
(1) The trap arm of a fixture that has a hydraulic load of not more than 1 ½ fixture units may be connected to the vertical section of a circuit vent, additional circuit vent, offset relief vent or yoke vent, provided that,
(a) not more than two fixtures are connected to the vent pipe,
(b) where two fixtures are connected to the vent pipe, the connection is by means of a double fitting, in accordance with Table 7.2.4.5., and
(c) the section of the vent pipe that acts as a wet vent conforms to the requirements regarding wet vents.
Tables & Figures referenced
Table 7.2.4.5 : Pipe Arrangement for DWV Fittings : Forming Part of Sentence 7.2.4.5.(1)
Loading Table 7.2.4.5…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.