Div. B › Part 7 › 7.4 › 7.4.9 — Size of Drainage Pipes

7.4.9.3 — Size of Fixture Outlet Pipes

Copied!
(1) Except as provided in Sentence (2), the size of every fixture outlet pipe shall conform to Table 7.4.9.3.
(2) The part of the fixture outlet pipe that is common to three compartments of a sink shall be one size larger than the largest fixture outlet pipe of the compartments that it serves.
(3) Where clothes washers do not drain to a laundry tray, the trap inlet shall be fitted with a vertical standpipe that is not less than 600 mm long measured from the trap weir and the top of the standpipe shall terminate above the flood level rim of the clothes washer it serves.
Tables & Figures referenced
Table 7.4.9.3 : Minimum Permitted Size of Fixture Outlet Pipe and Hydraulic Loads for Fixtures : Forming Part of Sentences 7.4.9.3.(1) and 7.4.10.2.(1)
Loading Table 7.4.9.3…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.