Div. B › Part 7 › 7.6 › 7.6.1 — Arrangement of Piping

7.6.1.1 — Design

Copied!
(1) Every fixture supplied with separate hot and cold water controls shall have the hot water control on the left and the cold on the right.
(2) Where hot and cold water are mixed and the temperature is regulated by a single, unmarked, manual control, a movement to the left shall increase the temperature and a movement to the right shall decrease the temperature.
(3) In a hot water distribution system of a developed length of more than 30 m or supplying more than 4 storeys, the water temperature shall be maintained by,
(a) recirculation, or
(b) a self-regulating heat tracing system.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.