7.4.10.5 — Conversion of Fixture Units to Litres and Gal/min

Copied!
(1) Except as provided in Sentence 7.4.10.3. (2), where the hydraulic load is to be expressed in litres, fixture units shall be converted as follows:
(a) when the number of fixture units is 260 or fewer, the load is 2 360 L, and
(b) when the number of fixture units exceeds 260, the load is 9.1 L for each fixture unit.
(2) Where the hydraulic load is to be expressed in gal/min, fixture units shall be converted in accordance with Table 7.4.10.5.
Tables & Figures referenced
Table 7.4.10.5 : Maximum Probable Drainage Rate, gal/min : Forming Part of Sentence 7.4.10.5.(2)
Loading Table 7.4.10.5…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.