Div. B › Part 7 › 7.4 › 7.4.10 — Hydraulic Loads

7.4.10.10 — Rain Leaders

Copied!
(1) No change in the size of a rain leader with a nominally horizontal offset is required if the offset,
(a) is located immediately under the roof,
(b) is not more than 6 m long, and
(c) has a slope not less than 1 in 50.
(2) If the horizontal offset is more than 6 m long, the rain leader shall conform to Table 7.4.10.9.
(3) The hydraulic load that is drained to a rain leader shall conform to Table 7.4.10.10.
Tables & Figures referenced
Table 7.4.10.9 : Maximum Permitted Hydraulic Load Drained to a Horizontal Storm Drainage Pipe : Forming Part of Sentences 7.4.10.9.(1) and 7.4.10.10.(2)
Loading Table 7.4.10.9…
Table 7.4.10.10 : Maximum Permitted Hydraulic Load Drained to a Circular Rain Leader : Forming Part of Sentence 7.4.10.10.(3)
Loading Table 7.4.10.10…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.