Div. B › Part 7 › 7.5 › 7.5.8 — Sizing of Vent Pipes

7.5.8.2 — Individual Vents and Dual Vents

Copied!
(1) The size of individual vents and dual vents shall be determined using Table 7.5.7.1. according to the largest trap served.
(2) When sizing an individual vent or a dual vent, the length is not taken into consideration.
Tables & Figures referenced
Table 7.5.7.1 : Minimum Permitted Size of Vent Pipe Based on Size of Trap : Forming Part of Sentence 7.5.7.1.(1)
Loading Table 7.5.7.1…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.