Div. B › Part 7 › 7.4 › 7.4.6 — Arrangement of Drainage Piping

7.4.6.4 — Protection from Backflow

Copied!
(1) Except as permitted in Sentence (2), a backwater valve that would prevent free circulation of air shall not be installed in a building drain or in a building sewer.
(2) A backwater valve may be installed in a building drain provided that,
(a) it is a “normally open” design conforming to,
(i) CAN/CSA-B70, “Cast Iron Soil Pipe, Fittings, and Means of Joining”,
(ii) CAN/CSA-B181.1, “Acrylonitrile-Butadiene-Styrene (ABS) Drain, Waste, and Vent Pipe and Pipe Fittings”,
(iii) CAN/CSA-B181.2, “Polyvinylchloride (PVC) and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings”, or
(iv) CAN/CSA-B182.1, “Plastic Drain and Sewer Pipe and Pipe Fittings”, and
(b) it does not serve more than one dwelling unit.
(3) Except as provided in Sentences (4) and (5), where a building drain or a branch may be subject to backflow,
(a) a backwater valve shall be installed on every fixture drain connected to it when the fixture is located below the level of the adjoining street, or
(b) a backwater valve shall be installed to protect fixtures which are below the upstream sanitary manhole cover when a residential building is served by a public sanitary sewer.
(4) Where more than one fixture is located on a storey and all are connected to the same branch, the backwater valve may be installed on the branch.
(5) A subsoil drainage pipe that drains into a sanitary drainage system that is subject to surcharge shall be connected in such a manner that sewage cannot back up into the subsoil drainage pipe.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.