Div. B › Part 7 › 7.5 › 7.5.8 — Sizing of Vent Pipes

7.5.8.4 — Vent Stacks, or Stack Vents

Copied!
(1) A vent stack, or stack vent shall be sized in accordance with Table 7.5.8.4. based on,
(a) the length of the vent stack or stack vent, and
(b) the total hydraulic load that is drained to the lowest section of soil or waste stack or stacks served by the vent pipe, plus any additional vent loads connected to the vent stack or stack vent.
(2) For the purposes of Table 7.5.8.4., the length of a stack vent or vent stack shall be its developed length from its lower end to open air.
(3) The minimum size of vent stack or stack vent shall be one-half the size of the soil or waste stack at its base.
(4) A stack vent serving a wet vent stack that is over 4 storeys high shall extend the full size of the wet vent to open air.
(5) Every sanitary building drain shall be provided with at least one vent that is not less than 3 in. in size.
Tables & Figures referenced
Table 7.5.8.4 : Size and Developed Length of Stack Vents and Vent Stacks : Forming Part of Sentence 7.5.8.4.(1)
Loading Table 7.5.8.4…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.