Div. B › Part 7 › 7.6 › 7.6.3 — Size and Capacity of Pipes

7.6.3.2 — Hydraulic Load

Copied!
(1) Except as provided in Sentence (3), the hydraulic load of a fixture or device that is listed in Table 7.6.3.2.A. shall be the number of fixture units given in the Table.
(2) Except as provided in Sentences (1) and (3), the hydraulic load of a fixture that is not listed in Table 7.6.3.2.A. is the number of fixture units listed in Table 7.6.3.2.D.
(3) Where fixtures are supplied with both hot and cold water, the hydraulic loads for maximum separate demands shall be 75% of the hydraulic load of the fixture units given in Tables 7.6.3.2.A. and 7.6.3.2.D. when using a detailed engineering design method.
(4) The hydraulic load of urinals and water closets with direct flush valves shall be the number of fixture units listed in Tables 7.6.3.2.B. and 7.6.3.2.C.
Tables & Figures referenced
Table 7.6.3.2.A : Sizing of Water Distribution Systems(1)(2) : Forming Part of Sentences 7.6.3.2.(1) to (3) and 7.6.3.4.(2), (3) and (5)
Loading Table 7.6.3.2.A…
Table 7.6.3.2.B : Sizing of Water Distribution Systems for Urinals with Direct Flush Valves : Forming Part of Sentences 7.6.3.2.(4) and 7.6.3.4.(5)
Loading Table 7.6.3.2.B…
Table 7.6.3.2.C : Sizing of Water Distribution Systems for Water Closets with Direct Flush Valves : Forming Part of Sentences 7.6.3.2.(4) and 7.6.3.4.(5)
Loading Table 7.6.3.2.C…
Table 7.6.3.2.D : Hydraulic Loads of Fixtures Not Listed in Table 7.6.3.2.A : Forming Part of Sentences 7.6.3.2.(2) and (3) and 7.6.3.4.(5)
Loading Table 7.6.3.2.D…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.