Div. B › Part 7 › 7.5 › 7.5.4 — Vent Pipes for Soil or Waste Stacks

7.5.4.2 — Vent Stacks

Copied!
(1) Except as provided in Sentence (2), every soil or waste stack draining fixtures from more than 4 storeys shall have a vent stack.
(2) A soil or waste stack that serves as a wet vent does not require a vent stack.
(3) The vent stack required by Sentence (1) shall be connected to a vertical section of the soil or waste stack at or immediately below the lowest soil or waste pipe connected to the soil or waste stack.
(4) Fixtures may be connected to a vent stack provided,
(a) the total hydraulic load of the connected fixtures does not exceed eight fixture units,
(b) at least one fixture is connected to a vertical portion of the vent stack and upstream of any other fixtures,
(c) no other fixture is connected downstream of a water closet,
(d) all fixtures are located in the lowest storey served by the vent stack, and
(e) the section of the vent pipe that acts as a wet vent conforms to the requirements regarding wet vents.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.