Div. B › Part 7 › 7.6 › 7.6.2 — Protection from Contamination

7.6.2.9 — Air Gap

Copied!
(1) An air gap shall not be located in a noxious environment.
(2) Every air gap shall be not less than 25 mm high and at least twice the diameter of the opening of the water supply outlet in height.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.