Div. B › Part 3 › 3.1 › 3.1.10 — Firewalls

3.1.10.1 — Prevention of Firewall Collapse

Copied!
(1) Except as permitted by Sentence (2), the connections and supports for structural framing members that are connected to or supported on a firewall and have a fire-resistance rating less than that required for the firewall, shall be designed so that the failure of the framing systems during a fire will not affect the integrity of the firewall during the fire.
(2) Sentence (1) does not apply to a firewall consisting of two separate wall assemblies each tied to its respective building frame but not to each other, provided each wall assembly is,
(a) a fire separation having one-half of the fire-resistance rating required for the firewall by Sentences 3.1.10.2. (1) and (2), and
(b) designed so that the collapse of one wall assembly will not cause the collapse of the other.
(3) A firewall is permitted to be supported on the structural frame of a building of noncombustible construction provided the supporting frame has a fire-resistance rating not less than that required for the firewall.
(4) Piping, ducts and totally enclosed noncombustible raceways shall be installed so that their collapse will not cause the collapse of the firewall.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.