Div. B › Part 3 › 3.2 › 3.2.9 — Standpipe Systems

3.2.9.6 — Water Supply for 38 mm Hose Connections

Copied!
(1) If a standpipe and hose system is required, the water supply shall be sufficient to provide a flow, measured at each of the two hydraulically most remote 38 mm diam hose connections,
(a) of not less than 380 L/min,
(b) for not less than 30 min,
(c) at a pressure of not less than 450 kPa, and
(d) of not less than 190 L/min from each of the two outlets simultaneously.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.