Div. B › Part 3 › 3.1 › 3.1.6 — Encapsulated Mass Timber Construction

3.1.6.9 — Exterior Cladding

Copied!
(1) Except as provided in Sentences (2), (3) and (6), cladding on an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction shall be noncombustible.
(2) Except as provided in Sentences (3) to (5), cladding on an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction is permitted to consist of,
(a) combustible cladding that,
(i) is not contiguous over more than 4 storeys,
(ii) represents not more than 10% of the cladding on each exterior wall of each storey,
(iii) is not more than 1.2 m in width,
(iv) has a flame-spread rating not more than 75 on any exposed surface, or any surface that would by exposed by cutting through the material in any direction,
(v) is separated from other portions of combustible cladding on adjacent storeys by a horizontal distance of not less than 2.4 m, and
(vi) is separated from other portions of combustible cladding by a horizontal distance of not less than 1.2 m,
(b) combustible cladding that,
(i) is not contiguous across adjacent storeys,
(ii) represents not more than 10% of the cladding on each exterior wall of each storey,
(iii) has a flame-spread rating not more than 75 on any exposed surface, or any surface that would be exposed by cutting through the material in any direction, and
(iv) is separated from other portions of combustible cladding on adjacent storeys by a horizontal distance of not less than 2.4 m,
(c) combustible cladding representing up to 100% of the cladding on exterior walls of the first storey, provided all portions of the cladding can be directly accessed and are located not more than 15 m from a street or access route conforming to Article 3.2.5.6., measured horizontally from the face of the building,
(d) except as provided in Sentence (4), a wall assembly that satisfies the criteria described in Clause 3.1.5.5. (1) (b), or
(e) a combination of noncombustible cladding and the cladding described in Clauses (a) to (d).
(3) The permitted area of combustible cladding referred to in Clause (2) (a) or (b) shall not exceed 5% of the cladding on each exterior wall of each storey where firefighting facilities cannot reach the building within 10 min of the alarm being received.
(4) An exterior wall assembly constructed in conformance with Section 6 of MMAH Supplementary Standard SB-2, “Fire Performance Ratings” is deemed to satisfy the criteria of Clause (2) (d).
(5) Except as provided in Article 3.2.3.10., where the limiting distance in Table 3.2.3.1.D. or Table 3.2.3.1.E. permits an area of unprotected openings of not more than 10% of the exposing building face, the construction requirements of Table 3.2.3.7. shall be met.
(6) A wall assembly conforming to Clause (2) (d) that includes combustible cladding made of fire-retardant-treated wood shall be tested for fire exposure after the cladding has been subjected to the accelerated weathering test specified in ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.
(7) Where combustible cladding conforming to Clause (2) (a) or (b) on an exterior wall of a fire compartment is exposed to combustible cladding conforming to Clause (2) (a) or (b) on an exterior wall of the same fire compartment or of another fire compartment, and the planes of the two walls are parallel or at an angle less than 135° measured from the exterior of the building, the different portions of combustible cladding shall,
(a) be separated by a horizontal distance of not less than 3 m, and
(b) not be contiguous over more than 2 storeys.
Tables & Figures referenced
Table 3.2.3.1.D : Unprotected Opening Limits for a Building or Fire Compartment that is Sprinklered : Forming Part of Article 3.2.3.1.
Loading Table 3.2.3.1.D…
Table 3.2.3.1.E : Unprotected Opening Limits for a Building or Fire Compartment that is Sprinklered : Forming Part of Article 3.2.3.1.
Loading Table 3.2.3.1.E…
Table 3.2.3.7 : Minimum Construction Requirements for Exposing Building Faces : Forming Part of Sentences 3.1.6.9.(5) and 3.2.3.7.(1) and (8)
Loading Table 3.2.3.7…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.