Div. B › Part 3 › 3.5 › 3.5.3 — Fire Separations

3.5.3.2 — Vertical Service Spaces for Dumbwaiters

Copied!
(1) A vertical service space containing a dumbwaiter shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.5.3.1. for the fire-resistance rating required by Subsection 3.2.2. for,
(a) the floor assembly above the storey, or
(b) the floor assembly below the storey, if there is no floor assembly above.
Tables & Figures referenced
Table 3.5.3.1 : Fire Separation for Vertical Transportation Space : Forming Part of Sentences 3.5.3.1.(1) and 3.5.3.2.(1)
Loading Table 3.5.3.1…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.