(1) Except where fire dampers, window assemblies and glass block are used as closures, closures of the same fire-protection rating installed on opposite sides of the same opening are deemed to have a fire-protection rating equal to the sum of the fire-protection ratings of the closures.
(2) Except as otherwise specified in this Part, every door, fire damper, window assembly or glass block used as a closure in a required fire separation,
(a) shall be installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”, and
(b) where required to have a fire-protection rating, shall have labels or classification marks to identify the testing laboratory.
(3) Except as otherwise specified in this Part, every smoke damper used as a closure in a required fire separation shall be installed in conformance with NFPA 105, “Smoke Door Assemblies and Other Opening Protectives”.
(4) If a door is installed so that it could damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent the damage.
(5) A leakage-rated door assembly rated in accordance with Sentence 3.1.8.4. (4) shall,
(a) be installed in fire separations in protected floor areas described in Clause 3.3.1.7. (1) (b),
(b) be installed in fire separations in care or care and treatment occupancies referred to in Sentence 3.3.3.5. (4) and installed in fire separations in retirement homes referred to in Sentence 3.3.4.11. (4),
(c) except as provided in Sentence (7), be installed in fire separations of public corridors serving dwelling units in storeys that are not sprinklered, and
(d) be installed in firewalls that are a horizontal exit referred to in Sentence 3.3.3.5. (3).
(6) Leakage-rated door assemblies required by Sentence (5) shall conform to NFPA 105, “Smoke Door Assemblies and Other Opening Protectives”.
(7) A leakage-rated door assembly need not be installed where a dwelling unit served by a public corridor has,
(a) a second and separate means of egress, or
(b) an open-air balcony that is sized to accommodate the number of occupants for which the dwelling unit is intended.