(1) Except as permitted by Articles 3.2.2.30. to 3.2.2.34., a building classified as Group A, Division 3 shall conform to Sentences (2) and (3).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7. (1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h,
(c) mezzanines shall have a fire-resistance rating not less than 1 h,
(d) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) If intended for occasional use for trade shows and similar exhibition purposes, the building referred to in Sentence (1) that is more than 1 500 m2 in building area shall be sprinklered.