Div. B › Part 3 › 3.16 › 3.16.1 — Scope

3.16.1.5 — Lighting

Copied!
(1) Walkways and platforms shall be equipped to provide illumination to an average level not less than 50 lx at floor or tread level and at angles and intersections at changes of level where there are stairs or ramps.
(2) Emergency lighting on walkways, platforms, unenclosed egress stairs and exits providing means of egress shall conform to not less than,
(a) the illumination level in Sentences 3.2.7.3. (2) and (3), and
(b) the duration in Sentence 3.2.7.4. (1).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.