3.4.6.3 — Maximum Vertical Rise of Stair Flights and Required Landings

Copied!
(1) No flight shall have a vertical rise of more than 3.7 m between floors or landings, except that a flight serving as an exit in a Group B, Division 2 or 3 occupancy shall have a vertical rise not more than 2.4 m between floors or landings.
(2) Except as provided by Sentence (3), a landing shall be provided,
(a) at the top and bottom of each flight of interior and exterior stairs,
(b) at the top and bottom of every section of ramp,
(c) where a doorway opens onto a stair or ramp,
(d) where a ramp opens onto a stair, and
(e) where a stair opens onto a ramp.
(3) A landing may be omitted at the bottom of an exterior stair or ramp, provided there is no gate, door or fixed obstruction within the lesser of,
(a) the width of the stair or ramp, or
(b) 1 100 mm.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.