(1) In a building or part of a building permitted to be of encapsulated mass timber construction,
(a) the flame-spread ratings required by Subsection 3.1.6. shall apply in addition to the requirements in this Subsection, and
(b) the flame-spread ratings for exits required by this Subsection shall also apply to any surface in the exit that would be exposed by cutting through the material in any direction, except that this requirement does not apply to doors, structural mass timber elements conforming to Sentence 3.1.6.4. (3), heavy timber construction and fire-retardant-treated wood.