Div. B › Part 3 › 3.13 › 3.13.4 — Means of Egress

3.13.4.2 — General Requirements

Copied!
(1) Except as provided in Sentence (2), escalators conforming to the requirements of Sentences 3.13.4.5. (3) and 3.13.4.6. (1) shall be acceptable as part of a required means of egress in a rapid transit station.
(2) Escalators forming part of a required means of egress shall not comprise more than one-half of the required egress capacity from any one level.
(3) Horizontal exits conforming to Sentence (4) may provide all of the required egress capacity from a rapid transit station.
(4) Horizontal exits to any one building shall not comprise more than one-half of the required egress capacity from any area within a rapid transit station.
(5) A protected route shall be provided with emergency ventilation conforming to Subsection 3.13.7.
(6) In an aboveground unenclosed station, the protected route is permitted to begin at the point of leaving the platform.
(7) In an enclosed or underground station, the protection for the protected route shall consist of,
(a) a fire separation having a fire-resistance rating not less than 1 h,
(b) construction having a fire-resistance rating not less than 1 h, or
(c) wired glass assemblies conforming to MMAH Supplementary Standard SB-2, “Fire Performance Ratings”.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.