Div. B › Part 3 › 3.1 › 3.1.11 — Fire Blocks in Concealed Spaces

3.1.11.4 — Fire Blocks between Vertical and Horizontal Spaces

Copied!
(1) Fire blocks conforming to Article 3.1.11.7. shall be provided,
(a) at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits in which the exposed construction materials within the space have a flamespread rating more than 25, and
(b) at the end of each run and at each floor level in concealed spaces between stair stringers in which the exposed construction materials within the space have a flamespread rating more than 25.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.