Div. B › Part 3 › 3.2 › 3.2.4 — Fire Alarm and Detection Systems

3.2.4.13 — Prevention of Smoke Circulation

Copied!
(1) If a fire alarm system is installed, an air handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air handling system,
(a) serves more than 1 storey,
(b) serves more than one suite in a storey,
(c) serves more than one fire compartment required by Sentence 3.3.3.5. (2) or Sentence 3.3.4.11. (2), or
(d) is not provided with fire dampers as permitted by Sentence 3.1.8.8. (4).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.