(1) If a fire alarm system is installed, an air handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air handling system,
(a) serves more than 1 storey,
(b) serves more than one suite in a storey,
(c) serves more than one fire compartment required by Sentence 3.3.3.5. (2) or Sentence 3.3.4.11. (2), or
(d) is not provided with fire dampers as permitted by Sentence 3.1.8.8. (4).