3.2.2.24 — Group A, Division 2, up to 6 Storeys, Any Area, Sprinklered

Copied!
(1) A building classified as Group A, Division 2, that is not limited by building area, is permitted to conform to Sentence (2) provided,
(a) except as permitted by Sentence 3.2.2.7. (1), the building is sprinklered, and
(b) it is not more than 6 storeys in building height.
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h, and
(c) all loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.