Div. B › Part 3 › 3.1 › 3.1.9 — Penetrations in Fire Separations and Fire-Rated Assemblies

3.1.9.3A — Penetration by Outlet Boxes

Copied!
(1) Except as provided in Sentences (2) and (3), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a fire stop that has an FT rating not less than the fire-resistance rating of the fire separation when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems”.
(2) Except as provided in Sentences 3.1.9.1. (2) and (3), noncombustible outlet boxes that penetrate a vertical fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided,
(a) they do not exceed,
(i) 160 cm² in area, and
(ii) an aggregate area of 650 cm² in any 9.3 m² of surface area, and
(b) the annular space between the membrane and noncombustible electrical outlet boxes does not exceed 3 mm.
(3) In addition to the requirements of Sentence (2), outlet boxes on opposite sides of a vertical fire separation having a fire-resistance rating shall be separated by,
(a) a horizontal distance of not less than 600 mm, or
(b) a fire block conforming to Article 3.1.11.7.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.