3.3.1.24 — Welding and Cutting

Copied!
(1) Except as provided in Sentence (2), welding and cutting operations shall be located in a room,
(a) separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h, or
(b) protected by an automatic fire extinguishing system.
(2) Sentence (1) does not apply to an industrial occupancy where the welding and cutting operations do not present a fire or explosion hazard to adjacent areas.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.