Div. B › Part 3 › 3.2 › 3.2.5 — Provisions for Firefighting

3.2.5.4 — Access Routes

Copied!
(1) A building that is more than 3 storeys in building height or more than 600 m2 in building area shall be provided with access routes for fire department vehicles,
(a) to the building face having a principal entrance, and
(b) to each building face having access openings for firefighting as required by Articles 3.2.5.1. and 3.2.5.2.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.