Div. B › Part 3 › 3.2 › 3.2.2 — Building Size and Construction Relative to Occupancy

3.2.2.35 — Group A, Division 4

Copied!
(1) Except as permitted by Sentences (2) and (3), a building classified as Group A, Division 4 shall be of noncombustible construction.
(2) Roof assemblies and supporting arches and columns are permitted to be of heavy timber construction.
(3) A building classified as Group A, Division 4 is permitted to be of combustible construction provided,
(a) the occupant load is less than 1 500, and
(b) the building has a limiting distance not less than 6 m.
(4) Sprinklers shall be installed in all spaces below tiers of seats in a building classified as Group A, Division 4 if those spaces are used for occupancy.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.