3.4.1.2 — Separation of Exits

Copied!
(1) Except as permitted by Sentence (2), if more than one exit is required from a floor area, each exit shall be separate from every other exit leading from that floor area.
(2) If more than two exits are provided from a floor area, exits are permitted to converge in conformance with Sentence 3.4.3.1. (2), provided the cumulative capacity of the converging exits does not contribute more than 50% of the total required exit width for the floor area.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.