Div. B › Part 3 › 3.1 › 3.1.6 — Encapsulated Mass Timber Construction

3.1.6.11 — Nailing Elements

Copied!
(1) Wood nailing elements are permitted to be used for the attachment of a material or assembly of materials to provide an encapsulation rating in a building or part of a building permitted to be of encapsulated mass timber construction, provided the concealed space created by the wood nailing elements is not more than 25 mm deep.
(2) Except as permitted by Sentence 3.1.6.16. (2) and Article 3.1.6.6., wood nailing elements are permitted to be used for the attachment of interior finishes in a building or part of a building permitted to be of encapsulated mass timber construction, provided the concealed space created by the wood nailing elements is not more than 50 mm deep and,
(a) exposed surfaces in the concealed space have a flame-spread rating not more than 25, or
(b) the concealed space is filled with noncombustible insulation.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.