Div. B › Part 3 › 3.13 › 3.13.3 — Safety Requirements Within Stations

3.13.3.3 — Service Rooms and Ancillary Spaces

Copied!
(1) An ancillary space in a rapid transit station shall be separated from the remainder of the floor area by a fire separation having a fire-resistance rating not less than 1 h.
(2) Except as provided in Sentence (3), a door opening from a service room onto a means of egress in a rapid transit station shall be located not less than 5 m from an escalator balustrade and from the top and bottom riser of a flight used as a means of egress from the rapid transit station.
(3) The requirements in Sentence (2) do not apply where,
(a) the service room is sprinklered, or
(b) there is a vestibule between the service room and the means of egress.
(4) Where a door from a service room opens onto a means of egress less than 5 m wide,
(a) the service room shall be sprinklered, or
(b) there shall be a vestibule between the service room and the means of egress.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.