(1) Except as provided in Sentence (2), not less than 90% of the exterior cladding on each exterior wall of buildings conforming to Article 3.2.2.43A. or 3.2.2.50A. shall consist of,
(a) noncombustible cladding, or
(b) a wall assembly that satisfies the criteria of Clause 3.1.5.5. (1) (b).
(2) Where a building is considered to face one street in accordance with Clause 3.2.2.10. (3) (b), the exterior cladding on each exterior wall of buildings conforming to Article 3.2.2.43A. or 3.2.2.50A. shall consist of,
(a) noncombustible cladding, or
(b) a wall assembly that satisfies the criteria of Clause 3.1.5.5. (1) (b).
(3) A wall assembly conforming to Clause (1) (b) or (2) (b) that includes combustible cladding made of fire-retardant-treated wood shall be tested for fire exposure after the cladding has been subjected to the accelerated weathering test specified in ASTM D2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing”.