Div. B › Part 3 › 3.2 › 3.2.4 — Fire Alarm and Detection Systems

3.2.4.22A — Residential Fire Warning Systems

Copied!
(1) Except where a fire alarm system is installed or required in a building, smoke detectors forming part of a residential fire warning system installed in conformance with CAN/ULC-S540, “Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance”, are permitted to be installed in lieu of all smoke alarms required by Article 3.2.4.22., provided that the system is,
(a) capable of sounding audible signals in accordance with Sentences 3.2.4.22. (8) and (12),
(b) provided with a visual signalling component in accordance with Sentences 3.2.4.22. (13) to (15),
(c) powered in accordance with Sentences 3.2.4.22. (5), and
(d) provided with a silencing device in accordance with Sentences 3.2.4.22. (10) and (11).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.