Div. B › Part 3 › 3.10 › 3.10.2 — Requirements for All Buildings

3.10.2.3 — Structural Fire Protection

Copied!
(1) Except as provided in Sentence (2) and Sentence 3.10.4.2. (1), the requirements in Subsections 3.2.1. and 3.2.2. shall apply.
(2) The first storey shall be subdivided into areas not more than 500 m2 by a masonry or reinforced concrete fire separation having a fire-resistance rating not less than 1 h, or it shall be sprinklered.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.