Div. B › Part 3 › 3.1 › 3.1.13 — Interior Finish

3.1.13.11 — Elevator Cars

Copied!
(1) The wall and ceiling surfaces of elevator cars shall have a flame-spread rating not more than 75.
(2) The wall, ceiling and floor surfaces of elevator cars shall have a smoke developed classification not more than 450.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.