Div. B › Part 3 › 3.2 › 3.2.9 — Standpipe Systems

3.2.9.3 — Hose Connections

Copied!
(1) If a standpipe system is required in a building, 38 mm diam hose connections shall be provided in each storey in the building.
(2) In addition to the requirements in Sentence (1), if a standpipe system is required, 65 mm diam hose connections shall be installed in each storey in the building if the building,
(a) is more than 25 m high, measured between grade and the ceiling of the top storey, or
(b) has a building area of more than 4 000 m2.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.