Div. B › Part 3 › 3.2 › 3.2.5 — Provisions for Firefighting

3.2.5.2 — Access to Basements

Copied!
(1) Direct access from at least one street shall be provided from the outdoors to each basement,
(a) that is not sprinklered, and
(b) that has horizontal dimension more than 25 m.
(2) The access required by Sentence (1) is permitted to be provided by,
(a) doors, windows or other means that provide an opening not less than 1 100 mm high and 550 mm wide, with a sill no higher than 900 mm above the inside floor, or
(b) an interior stairway immediately accessible from the outdoors.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.