Div. B › Part 3 › 3.12 › 3.12.5 — Emergency Provisions for All Public Spas

3.12.5.1 — Lighting and Emergency Provisions

Copied!
(1) In addition to the requirements of this Subsection, public spas shall comply with the requirements of Sentences 3.11.10.1. (1) to (6).
(2) An emergency telephone directly connected to an emergency service or to the local telephone utility shall be installed within 30 m of the public spa.
(3) All pumps used in a public spa shall be capable of being deactivated by an emergency stop button that is,
(a) clearly labelled, and
(b) located at a point that is,
(i) readily accessible to and within sight of persons using the public spa, and
(ii) within 15 m of the public spa.
(4) The emergency stop button required in Sentence (3) shall,
(a) be a switch separate from the public spa’s timing device,
(b) activate an audible and a visual signal when used, and
(c) have an emergency sign conforming to Sentence 3.11.10.1. (14).
(5) If a public spa and public pool are located in the same room or space, the emergency stop buttons required in Sentences (3) and 3.11.10.1. (12) shall deactivate all pumps serving the public spa and public pool.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.